Electrical Wiring for all models

To Install the wiring for the Y series spa control, you’ll need Phillips screwdriver and a flat screwdriver.

Loosen the screws of the spa pack cover and remove it. Remove 51/2” (142mm) of cable insulation. Strip away 1” (25mm) of each wire insulation. Pull the cable through the cutout of the box and secure it with a strain relief (1” NPT strain relief; hole diameter 1.335” (33.9mm)

(For CE use an IEC certified plastic Bushing that will maintain the IPX5 rating).

Make sure that only the uncut sheathing is clamped at this opening. Make sure that the terminal block case clamps are lowered before inserting wires. Push the color-coded wires intro the terminals as indicated on the sticker and use the flat screwdriver to tighten the screws on the terminals.

After making sure wire connections are secure, push them back into the box and replace the cover, tighten cover screws (torque to 8in.lb max [0.9N.m]).

Connect the bonding conductor to the bonding lug on the front of the Y series spa pack (a grounded electrode conductor shall be used to connect the equipment grounding conductors).

Electrical Wiring: North American model
Refer to wiring diagram in the enclosure box lid for more information.

For 240V (4 wires)
Correct wiring of the electrical service box, GFXI, and pack terminal Block is essential.
Call an electrician if necessary

For 120 V (*3 wires)
*if Connected to a 3 wire system, no 240 V component will work

Note: To convert model to a 120V system, the white (common) accessory wire must be moved. See wiring diagram for details.
Electrical Wiring: in.ye European model
Refer to wiring diagram in the enclosure box lid for more information.

1-phase = connect PJ1 between P7 and P13, connect PJ2 between P10 and P74.

2-phase with single neutral
connect PJ1 between P7 and P10, connect PJ2 between P13 and P74.

3-phase with single neutral
connect PJ1 between P7 and P10, connect PJ2 between P11and P13.

3-phase Delta
connect PJ1 between P7 and P10, connect PJ2 between P13 and P74.

In.ye.ce 230V or 230/400V

Correct wiring of the electrical Service Box, RCD, and pack Terminal block is essential!
Call an electrician if necessary.

Warning!
In,ye,ce models must always be connected to a circuit protected by a Residual-Current device (RCD) having a rated operating residual-current not exceeding 30 mA.